EDF reports EBD anomaly

28 February 2011


French nuclear utility EDF has declared an anomaly affecting the bearing bushings of its back-up diesel generators at its Blayais, Bugey, Chinon, Cruas, Dampierre, Gravelines, Saint-Laurent and Tricastin power stations to the French Nuclear Safety Authority.

Generic illustration of emergency power sources of French nuclear power plants
Counterclockwise from top left: The primary high-tension power lines carry 400,000V. Turbine hall and alternator. Auxiliary external supply. First emergency backup diesel engine. Second emergency backup diesel engine.


The anomaly is rated Level 1 on the international INES scale, except at Tricastin, where it is rated Level 2 ('incident').

Each nuclear power plant has five diverse, permanently-available sources of electricity. This allows for the continuing operation of all equipment, including safety systems, even in case of failure of grid supply. Power is sourced from two high-voltage power lines and three back-up facilities. For 900MW reactors, there are three diesel generators. Plants with 1350MW and 1450MW reactors have two diesel generators and a combustion turbine. The three back-up sources of power must be permanently maintained as fit for purpose, so that they can in the event of failure of the two standard sources of power, supply the electricity needed to operate the safety systems.

The anomaly is caused by premature wear. EDF said that it is of no consequence to the operation and safety of the facilities in question. EDF declared that it would preventively replace the bushings in question. Maintenance procedures, which can be performed while the reactors are in operation, began on 12 February 2011.

Inspection revealed premature wear on a metal component known as a bearing bushing fitted to the diesel engines of the back-up generators equipping nuclear power stations. This premature wear is a deviation from nuclear safety rules. These require that electrical power supply components are fit for purpose at all times, including when not called upon for normal power station operations, as a result of inspections and regular maintenance. Hence, the discovered anomaly has prompted to reinforce the maintenance procedures on the diesel generators. Since 2009, these bearing bushings have been fitted to 26 diesel-fired generators in eight 900 MW nuclear power stations.

Each nuclear power unit has three back-up diesel generators. At the four-unit Tricastin site, the bushings need to be replaced on the third diesel generator. This generator will, if necessary, pick up load to allow for the replacement of the bushings on the first two generators of units 3 and 4. This is not the case for the other affected power stations. Maintenance and replacement operations on the third back-up diesel generator at Tricastin took place on 17 February 2011.




Privacy Policy
We have updated our privacy policy. In the latest update it explains what cookies are and how we use them on our site. To learn more about cookies and their benefits, please view our privacy policy. Please be aware that parts of this site will not function correctly if you disable cookies. By continuing to use this site, you consent to our use of cookies in accordance with our privacy policy unless you have disabled them.